MLY02.100

Diode redundancy module
24V, 10A

  • Redundancy module for building redundant systems
  • Two 5A inputs, one 10A output
  • Only 0.9V voltage drop between input and output under full load
  • Full output current between -40 and +60°C
  • Quick-connect spring-clamp terminals
  • Adapter for Wall Mounting includet
DC Output12-48Vdc
10A
Input DC 12V-48V  (± 25%)
Size (WxHxD)45 x 75 x 91mm
Weight140g
Product Status Stock item 
Technical Data

Input Data
Input Current2*5A
Nominal Current Per Input5A
DC-Input Voltage DC 12V-48V  (± 25%)
Voltage Drop800mV (H2)

Output Data
Output Current 10A
Output Current Range10A  (F2)
Output Current Short circuit max.16.0A (G2)

Overview
Size (WxHxD)45mm x 75mm x 91mm
Weight per Piece (excluding packing)140g
Operat. Temperature Range-40°C ... +70°C
Derating0.25W/°C at >+60°C
Mounting Method Din-Rail
Power Losses, typ.4.0W
Power Losses no Load0W
MTBF SN 29500 @ 40°C (h)58.000.000h
Connection methodspring clamb terminals
Footnotes
F2)50% higher currents are allowed up to 5s
G2)Current at voltage <6V
H2)1+1 -redundancy (=50% of the nominal current) and symmetrical input currents
Commercial Information

Overview
Article NumberMLY02.100
UPC Code875404000143
Country of originCN
Product Status Stock item 
E ClassificationeClass 5.1 27242213
eClass 6.x 27049005
eClass 7.x 27049005
eClass 8.0 27210902
eClass 9.0 27040701
ETIM 4.0 EC000599
ETIM 5.0 EC002540
HS Code HS 85044082
Warranty Period (Month)36
Packaging Unit1pc